Interaction between the Voltage-Droop and the Frequency-Droop Control for Multi-Terminal HVDC Systems - CentraleSupélec
Communication Dans Un Congrès Année : 2015

Interaction between the Voltage-Droop and the Frequency-Droop Control for Multi-Terminal HVDC Systems

Résumé

MTDC systems need to provide a high level of reliability as well as efficient support to the interconnected AC grids. This can be achieved by equipping each converter with a dual controller combining both the voltage-droop and the frequency-droop control techniques. In this article, the theory behind the coupling between the two droops is investigated and an electromagnetic transient study of a 5-terminal HVDC grid is discussed to validate the theoretical results. The use of the dual controller allows the whole system to be more flexible. However, the frequency droop coefficient must be corrected to comply with the TSO's requirements.
Fichier principal
Vignette du fichier
ACDC_CONFERENCE_Manuscript.pdf (520.17 Ko) Télécharger le fichier
Origine Fichiers produits par l'(les) auteur(s)
Loading...

Dates et versions

hal-01243994 , version 1 (15-12-2015)

Identifiants

Citer

Samy Akkari, Marc Petit, Jing Dai, Xavier Guillaud. Interaction between the Voltage-Droop and the Frequency-Droop Control for Multi-Terminal HVDC Systems. AC and DC Power Transmission, 11th IET International Conference on, Feb 2015, Birmingham, United Kingdom. ⟨10.1049/cp.2015.0036⟩. ⟨hal-01243994⟩
179 Consultations
1793 Téléchargements

Altmetric

Partager

More